Đầu dò báo khói nhiệt kết hợp GST C-9101
- C-9101 Conventional Combination Heat/Photoelectric Smoke Detector is consisted of smoke sensing and semi-conductor temperature sensing parts in processing and circuitry. Matching with P-9907 Active End of Line Unit (AEOL), it can be connected with conventional fire alarm control panel or intelligent fire alarm control panels through I-9319 Addressable Zone Monitor Unit to execute signal processing. This non-addressable detector has the advantages of both conventional photoelectric detector and rate of rise and fixed temperature heat detector. Just because of the combination technology of smoke detector and heat detector, it overcomes the non-sensitivity to dark smoke particles of ordinary scattering type photoelectric detectors. It can also pick up fire with obvious rise of temperature such as alcohol fire, thus extending the application range.
- Drift compensation to suit environment changing extensively.
- Integrated algorithm for analyzing fire, improving the sensitivity highly.
- Self-diagnostic.
- Removable innovative sensing chamber, easy for maintenance.
- Reporting dirt fault for contaminated chamber.
- Remote indicator output available.
- 3 levels sensitivities programmable; Level 1 complies with EN 54-7. Fix temperature or rate of rise programmable, rate of rise mode complies with EN 54-5.
Thông số kỹ thuật
Model C-9101
Operating Voltage 24VDC (16VDC~28VDC)
Standby Current ≤100μA
Alarm Current 10mA≤I≤40mA
Maximum Ripple Voltage 2V (peak-to-peak value)
Indicator Red: flashes in normal and illuminates in alarm.
The LED is quiet in fault. And it lights and then turns out about every three seconds periodically when reported dirty.
Remote Indicator Output Directly connecting with indicator (built-in 5.1kΩ resistor, maximum output current is 5.0mA). Quiet in normal condition. Flashes in alarm.
Alarm Clear Instantaneous Power-off (10s MAX., 1.5VDC MAX.)
Power-up Time ≤10s
Action Temperature 62℃
Class A2R
Wiring Polarized 2-core for detection zone cable.
Polarized 2-core for remote indicator.
Ingress Protection Rating IP22
Environment Temperature -10℃~+50℃
Relative Humidity ≤95%, non condensing
Material of Enclosure ABS
Dimensions Diameter: 100mm
Height: 56mm (with base)
Mounting Hole Distance 45mm~75mm
Weight 126g
Đang cập nhật...