Đầu dò báo nhiệt địa chỉ kèm đế COOPER CAPT340/CAB300
- Cooper offers a comprehensive range of conventional sensors that are compatible with: Cooper, Menvier and JSB conventional control panels.
- LPCB 3rd party approved/ CPD approved.
- Low profile design.
- 360° viewable LED design.
- Removable detector chamber for cleaning.
- Common mounting base.
- New enhanced detectors feature Dual LEDs.
- Drift compensation and Chamber monitoring (Optical & Photo-Thermal).
Đầu dò báo nhiệt địa chỉ kèm đế COOPER CAH330/CAB300
- This range of intelligent addressable sensors have been specifically designed to operate with Eaton’s intelligent addressable fire systems.
- All sensors are third party approved to the relevant section of EN54 (part 7 for smoke detectors, part 5 for heat detectors and part 17 for short circuit isolators).
- The CAH330 can be set to one of 3 modes 77ºC / 92ºC and rate of rise. These sensors are designed to be used in environments where the ambient conditions might cause false alarms if smoke detection were to be used, for example where there is a high level of dust, fumes, steam or smoke under normal conditions.
Features
- Soft addressed.
- Integral short circuit isolator.
- Single address.
- Wide range of sensor types.
- 360° visibility LED using lightpipe technology.
- Drift compensation.
- Aesthetically pleasing.
Benefits
- Quick and simple to install.
- Single “multi-mode” heat sensor.
- Wide viewing angle for increased LED visibility.
- Common mounting base.
- Positive “lock” indication.
- Discreet design for incorporation into any decor.
- Easy to maintain/service.
Đặc tính kỹ thuật
Model CAPT340
Description Multi-Mode heat sensor
Standards EN54 Pt5 2000 + A1:2002, EN54 Pt17
Operating volatage 18V dc to 30V dc
Standby current 220μA (max)
Alarm current 5mA (max)
Addressing mode Auto address
Specification
Mounting position Ceiling in open areas
Mounting options Surface mount with CAB300 base
Area coverage 100m² (subject to local standard)
System wiring Min. 1.5mm, 2 core loop or spur
Heat class
Rate of Rise A1R
Fixed Heat 77ºC BS
Fixed Heat 90ºC CS
Alarm Temperature (static)
AIR 60ºC
BS 77ºC
CS 90ºC
Indication 360° visibility light pipe
Environmental
Operating temperature -10°C to +60°C
Humidity (non condensing) 0 to 95% RH
Physical
Construction PC/ABS
Colour - Ral No White - 9003
Dimensions excel base (Dia x D) 101mm x 43mm
Dimensions incl base (Dia x D) 104mm x 55mm
Weight (without base) 76g
IP Rating IP30
Compatibility
Suitable for use with Eaton: Cooper addressable fire systems
Đang cập nhật...