MODEL |
AR-MP6KRT |
AR-MP10KRT |
Capacity |
6000VA/6000W |
10000VA/10000W |
INPUT |
|
Nominal voltage |
208/220/230/240Vac |
Input voltage range |
110~286Vac |
Frequency range |
40~70Hz (50/60Hz Auto-Sensing) |
Power factor |
≥0.99 |
|
Max.voltage:220V:+25% (Optional+10%,+15%,+20%) 230V:+20% (Optional+10%,+15%,+20%) |
Bypass voltage range |
240V:+15% (Optional+10%) |
|
Min.voltage:-45% (Optional-20%,-30%) |
OUTPUT |
|
Output voltage |
208/220/230/240Vac |
Power factor |
0.9 |
Voltage regulation |
±1% |
Output frequency |
Line Mode |
±1%/±2%±/±4%/±5%/±10% of the rated frequency (Optional) |
Bat. Mode |
(50/60±0.1%)Hz |
Crest factor |
3:01 |
Harmonic distortion (THDv) |
≤2% Linear load |
≤5% Non linear load |
Transfer time |
AC mode to Bat.Mode |
0ms |
Inverter to Bypass |
0ms |
Output waveform |
Pure Sinewave |
Overload |
Line Mode |
Load≤110% last 60min; ≤125% last 10min; ≤150% last 1min; >150% turn to bypass mode immediately |
Bypass Mode |
40A (Breaker) |
63A (Breaker) |
Efficiency |
94% |
BATTERY |
|
Battery voltage |
±96/±108/±120Vdc (Adjustable) |
±120Vdc |
±96/±108/±120Vdc (Adjustable) |
±120Vdc |
Capacity (Standard unit) |
9Ah/12V (7Ah/12V optional) |
Typical recharging time |
6~8 hours (to 90% of full capacity) |
Charging current |
1A (Standard unit); Long run unit Max.current 10A (Charging current can be set according to battery capacity) |
INDICATORS |
|
LED display |
Line mode,Bat.mode,ECO mode,Bypass mode,Battery low voltage,Overload & UPS fault |
LCD display |
Input voltage,Input frequency,Output voltage,Output frequency,Load percentage, |
Battery voltage,Inner temperature& Remaining battery backup time |
ALARM |
|
Battery mode |
Beeping every 4 seconds |
Battery low |
Beeping every second |
Overload |
Beeping twice every second |
Fault |
Continously beeping |
PHYSICAL |
|
Dimension W x D×H (mm) |
440 x 625 x 86.5 |
Net weight (kg) |
16 |
18 |
ENVIRONMENT |
|
Operating temperature |
0℃~40℃ |
Storage temperature |
-25℃~55℃ |
Humidity range |
20~95%RH @ 0~40℃ (Non condensing) |
Altitude |
<1500m,derating required when>1500m |
Noise level |
<55db at 1 Meter |
<58db at 1 Meter |
STANDARDS |
|
Safety |
IEC/EN62040-1,IEC/EN62477-1 |
EMC |
IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 |