Micro Single Channel Output Units COOPER MCOM-S
- The (MCOM-S) is identified by the panel as a sounder and does not reset when put into ''silence'' mode, only resets once panel has been reset.
Benefits
- Quick and simple to install.
- Compact size.
- Soft Addressed.
- Integral short circuit isolator.
- Plug and play, no hard addressing required.
- No external short circuit isolator required.
Thông số kỹ thuật
Description Micro zone monitor unit
Standards EN54 Pt17 & Pt18
Specification
Operating Voltage 18.5V dc to 30V dc
Quiescent Current 2.6mA (nom)
Load With 20 Detectors, and Unlimited Callpoints 3.2mA (nom)
Alarm Load With 20 Detectors, and Unlimited Callpoints 8.0mA (nom)
Detector Zone
Detectors per Zone 20 (max)
End of Line Monitor Active end of line unit - EOLM-1
Fire Input Trigger Resistance 680Ω (nom)
Short Circuit Fault Threshold Resistance 100Ω (max)
Open Circuit Fault Threshold Resistance 39kΩ (min)
Environmental
Operating Temperature -10ºC to +60ºC
Humidity (non condensing) 0 to 95% RH
Physical
Construction PC/ABS
Dimensions (H x W x D) 63mm x 35mm x 18.5mm
Weight 0.28kg
Ingress Protection IP40
Compatibility
Suitable for use with Menvier intelligent addressable fire systems
Recommended loop/cable type Fire Tuff, FP200 MICC