Micro Zone Monitor Unit COOPER MIU872
- The MIU872 is a single zone input, soft addressed, micro interface, incorporating integral short circuit isolators.
Features
- Quick and simple to install.
- Accepts a zone of Menvier conventional detector heads and callpoints (detectors must be connected via the Cooper CDBB300 mounting base).
- Only takes a single address.
- Input monitored for open and short ground trouble.
- Active end of line monitoring.
- Built in short circuit isolator.
Benefits
- Plug and play no hard addressing required.
- Easy to expand a system using existing wiring.
- No external short circuit isolator required.
Thông số kỹ thuật
Description Micro zone monitor unit
Standards EN54 Pt17 & Pt18
Specification
Operating Voltage 18.5V dc to 30V dc
Quiescent Current 2.6mA (nom)
Load With 20 Detectors, and Unlimited Callpoints 3.2mA (nom)
Alarm Load With 20 Detectors, and Unlimited Callpoints 8.0mA (nom)
Detector Zone
Detectors per Zone 20 (max)
End of Line Monitor Active end of line unit - EOLM-1
Fire Input Trigger Resistance 680Ω (nom)
Short Circuit Fault Threshold Resistance 100Ω (max)
Open Circuit Fault Threshold Resistance 39kΩ (min)
Environmental
Operating Temperature -10ºC to +60ºC
Humidity (non condensing) 0 to 95% RH
Physical
Construction PC/ABS
Dimensions (H x W x D) 63mm x 35mm x 18.5mm
Weight 0.28kg
Ingress Protection IP40
Compatibility
Suitable for use with Menvier intelligent addressable fire systems
Recommended loop/cable type Fire Tuff, FP200 MICC