Module giám sát lối vào NOHMI FRRU004-MCM
- The Miniature Contact Module (FRRU004-MCM) is used to monitor the contact status of an initiating device that contains a normally open contact.
- The FRRU004-MCM can be programmed in the panel to supervise either a Normally-open or Normally-closed contact on the Fire Alarm Control Panel (FACP). When the Normally-open contact is selected, and the contact is closed, the FRRU004-MCM reports its condition to FACP. Likewise when the Normally-closed contact is set to a supervising condition, and the contact is opened, the FRRU004-MCM reports its condition to FACP. FRRU004-MCM supervises an open circuit of wiring connected to the terminal C and NO (NC) contact. The FRRU004-MCM is generally used to monitor pull stations and other devices where the module is installed in an electrical box or enclosure. The contact utilizes a terminal block that is covered in accordance with UL requirements to protect from inadvertent shorts and ground faults.
Features
- NFPA Class A (Styles 6 & 7) and Class B (Style 4) for SLC.
- NFPA Class B (Style B) for IDC.
- Electronic address setting.
- Mini-sized unit.
- Easy installation.
Đặc tính kỹ thuật
Model FRRU004-MCM
Rated voltage range of SLC input power (S+,S-) 22.0 to 24.0V
Maximum SLC 24 VDC standby current (S+,S-) 250µA
Maximum SLC 24 VDC alarm current (S+,S-) 250µA
IDC input circuit wiring style Class B (Style B)
End-of-line resistor for IDC 5.1kΩ, 1/2W
Maximum wiring resistance of IDC 100Ω
Maximum wiring capacitance of IDC 1µF
Operating temperature range 0°C to 49°C (32°F to 120°F)
Operating humidity range 0 to 93% (non-condensing)
Dimensions 65.5mm (2.58 inches) (H) × 59mm (2.32 inches) (W) × 24mm (0.94 inch) (D)
Applicable electrical box for installation North American 64mm (2-1/2 inches) deep single-gang box