Trung tâm báo cháy 10 kênh NOHMI FAPN105N-R-10L
- On receiving a fire signal from a fire detector or a manual alarm box, the FAPN202-R-5L conventional fire alarm panel produces visual alarms to alert the alarm panel operator. It also produces alarms to alert the occupants of the building premises. The FAPN202-R-5L conventional fire alarm panel indicates the alarm points on individual zone lamps.
Features
- Conventional type 5 fire zones (No programming required).
- Alarm verification type (Alarm verification time: 60 seconds).
- Various test functions: Fire indication test, alarm verification time test, auxiliary power supply test, automatic after-test resetting.
- Self diagnosis system.
- Misoperation inhibit function.
- Back-up power supply (Ni-Cd battery, 24VDC).
- Large fire alarm symbol for easy visual recognition.
- Durable LED indicators.
- Removable front cover for easy installation and maintenance.
- Built-in surge arrester for power lines.
Đặc tính kỹ thuật
Type Conventional type
Power supply 220VAC 50/60Hz
Auxiliary power supply Ni-Cd battery (24VDC, 0.45Ah)
Circuit voltage 5, 24, 48 VDC, 24VDC
Alarm Verification time Thermal detector: 10 sec, Smoke detector: 60sec
Power consumption Monitoring: 25VA max. approx
Alarm: 40VA max, approx
Maximum number of devices supported Spot type smoke detectors: 30/zone (max.150/panel)
Alarm bells: 15 (24VDC, 10mA/bell)
Location lamps: 5 (30V, 2W/lamp) 15(24V, 24mA/LED), 21 (24V, 15mA/LED)
Ambient temperature and humidity 0 to 40°C, 20 to 85% (RH)
Alarm input circuit loop resistance Less than 50Ω/Loop
End-of-Line resistor 10kΩ, 1/2W
Materials (enclosure) ABS resin with 94UL-V2 flammability rating
Color Off-white (Nohmi White): Approximating Munsell N8.7 or equivalent
Weight Approx. 3kg