Trung tâm báo cháy 16 kênh ZETA PMP16
- The Premier M Plus control panels are designed to fulfil the requirements of EN54 parts 2 & 4 as well as being easy to install, operate and maintain.
- 4 Common sounder circuits (150mA each).
- Optional add-on zonal sounder circuits (50mA Max.).
- Serial repeater output.
- Auxiliary supply (29 Volts, 250mA).
- Zone & sounder disablement facility.
- Sounder delay facility.
- Zonal to common timer (when fitted with zonal sounder boards).
- One man test mode.
Đặc tính kỹ thuật
Model PMP16
Detection Zones 16
Mains Voltage 230V AC +10% / -15% @ 50/60 Hz
System Voltage 24V DC (nominal)
Zone Voltage 21V DC
Sounder Alarm Output 4 x 150mA @ 24V DC
Fault Relay Output 1 x relay SELV @ 1A maximum
Fire Relay Output 1 x relay SELV @ 1A maximum
Zone Capacity 32 Devices
Sounder Activation Delay 0 – 9 minutes in 1 minute increments
Zone End Of Line IN4002 Diode
Sounder End Of Line 10KΩ Resistor
Charger Voltage 28.4V DC (batteries disconnected)
Zone Short Circuit Protection 100mA
Charger Short Circuit Protection Batteries less than 20V
Charger Size 3.0 Amp
Operating Temperature 0°C - 50°C
Enclosure Size 485 x 477.5 x 125mm