Trung tâm báo cháy 2 kênh GST GST-102A
- The GST-102 conventional fire control panels provide two zones of fire detection. All panels have been designed to offer high standards of performance, reliability and quantity and comply fully with BS5839, Part 4, 1988 and EN 54 parts 2 and 4. Each zone can be connected with 15 conventional fire detectors.
- Microprocessor controlled SMT Electronics.
- Compliant with EN54 part 2&4, & BS5839, Part 4, 1988.
- Both end of line resistors and active end of line can be used.
- Programmable sounder circuits and outputs.
- Zone Isolate control.
- Fully monitored sounder circuits.
- Key control evacuate over-ride.
- Class change terminals for remote control.
- Up to 15 fire detectors and infinite manuals call points each zone.
Thông số ky thuật
Model GST 102
Operating voltage 220VAC ± 15% , 50Hz
Standard BS5839, Part 4, 1988 and EN 54 parts 2 and 4
Approval CE, LPCB
Operating Temperature -10°C to 40°C @ 95% relative humidity
Number of Zone Two zone
Zone Capacity 15 detectors (AOL);25 detectors (EOLR)
Standby Batteries 5AH, 24hours monitoring state
Output Voltage 20VDC to 28 VDC
Static Loading Current 2.5mA (when connected with 15 conventional detector)
Fire Alarming Resistance 150Ω-1.5KΩ (normal 470Ω)
End Of Line resistor 4.7KΩ or AEOL (Active End Of Line)
No. of Sounder Output 2
Sounder Output Current 1 Ampere (500mA per output)
Sounder Output Voltage 20VDC to 28 VDC
Aux.Power Output 20VDC to 28 VDC
Application Indoor use
Materials and colour Coated Metal / Grey
Dimension 380 x 320 x 95 mm