Trung tâm báo cháy 4 kênh ZETA IN4
- Access via password – removes problem of lost keys.
- One man test facility.
- Disablement facility for zones & sounders.
- Space for up to 3Ah batteries.
- Sounder delay option.
- 4 sounder circuits.
- Sounder circuits 3 and/or 4 can be configured as Aux 24V supplies.
- Meets all requirements of latest EN54 part 2 and part4.
Đặc tính kỹ thuật
Model IN4
Part No 37-652
Mains Voltage 230V AC +10% / -15% @ 50/60 Hz
System Voltage 24V DC (Nominal)
Zone Voltage 21V DC (Nominal)
Sounder Alarm Output 4 x 150mA @ 24V DC
Fault Relay 1 x Volt Free Relay, SELV @ 1A Max
Fault Relay 1 x Volt Free Relay, SELV @ 1A Max
Zone Capacity 32 devices per zone
Remote sounder operation Via N/O contact connected to Class Change
Sounder Activation Delay 0 to 10 minutes in 1 minute increments
Zone End of line 1N4002 Diode (Cathode Stripe to Zone +ve)
Sounder End of Line 10K resistor
Charger Voltage 27.6V
Battery cut off Battery voltage less than 20V
Battery Internal Resistance limit 0.9 ohm
Enclosure size 371 x 302 x 93 (mm)
Weight 3 kg (Excluding Batteries)
Maximum battery space 2 x 3.4 Ah, 12 Vdc sealed lead aci