Trung tâm báo cháy 8 vùng SIEMENS FC123-ZA
- The FC123-ZA compacts fire control panels with an integrated operating unit for 4 zones.
- Processes signals from the 110-series/ DS11 and SynoLINE300/600 series.
- The control unit has been designed to be very simple to use while offering exceptional flexibility via a comprehensive feature list.
- All detector lines are monitored for ground faults.
- Adaptation of the customer text directly on the panel via menu navigation.
- Up to 1000 events can be stored according to various criteria.
- Automatic summer/winter time change.
Thông số ky thuật
Model FC122-ZA-8 zones
Mains voltage AC 97…127 V
AC 196…253 V
Power consumption 70 W
Operating voltage DC 21…28.6 V
Max. nominal output current without battery charging (I max b) Max. 2.5 A
Battery capacity 2x 12V, up to 17 Ah
Battery monitoring Yes
Mains monitoring Yes
Connectable detector series 110-series/ DS11/ SynoLINE300/ 600
Number of lines 8
Number of detectors per line Max. 32
Slots for relay cards 2
Emergency current Up to 72 Ah
Operating temperature -5…+40 °C
Storage temperature -20…+60 °C
Humidity (no condensation permitted) ≤95 % rel.
Dimensions (W x H x D) 430 x 399 x 124 mm
Protection category (IEC 60529) IP30
Đang cập nhật...