Trung tâm điều khiển 4 zones COFEM CLVR04Z
- CLVR Control panel up to 4 zones.
- 2 supervised sounder outputs, delayed from 0 to 10 minutes, and protected by a fuse.
- 1 alarm output through a dry contact NO/NC (normally open/ normally closed).
- 1 fault output through a dry contact NO/NC (normally open/ normally closed).
- 2 auxiliary outputs 30V/DC supervised and protected by a fuse to feed external (magnetic fire doors, sounders, etc).
- Available testing mode to facilitate the quick and easy verification of the sensors and call points.
- It allows to configure the open line, alarm detector and alarm call point threshold, to adjust to the operation with other detectors.
- It allows to configure the last detection zone as a supervision input of a external protection fire system with a fault indication.
- Metallic chest with frontal bolted door, 4 predrilled of 28 mm and one rectangular else of 140 x 20 mm for electric wiring and space for 2 batteries of 7Ah.
- RS485 MODBUS protocol on-demand.
- Possibility of software ON-LINE on PC using MODBUS functionality.
- CONTACTID on-demand.
- Certified according to EN 54-2 & EN 54-4 standards and CE mark.
Đặc tính kỹ thuật
Input voltage 110/230VAC 50/60Hz
Output voltage 21V Nominal
Maximum consumption 70 VA to 230 V/AC
Batteries 2x12V7 Ah SLA
Max. voltage 30V output 0,75A/ 1,50A
Battery charger 500 mA 27 V/DC 20ºC
Devices per zone 32
Control panel power supply 2,2 A
Maximum current per zone 2 mA (standby)
End of line capacitor 4 K7
Sounder output voltage 30 V/DC 2 A
Fault output Yes, dry contact
Environmental conditions -10ºC +50ºC
Size 363 x 331 x 96 mm
Weight (without batteries) 4,3 Kg
Standar EN 54-2, EN 54-4&EN 12094-1
Sounder output fuse S1 1A/ 1,85A Autoreset
Sounder output fuse S2 1A/ 0,75A Autoreset
Đang cập nhật...